ORION

Mains supply voltage
85-264V 50/60 Hz
Internal power supply
Min. 20 V DC – Max. 30 V DC (28.5 V DC nominal) Max. Ripple 1 V peak-peak
Total output current
1,7A @230Vac
Supply and battery
charger monitored? YES
Batteries monitored YES
Max Battery size 2 x 12V
7AH SLA
Mains Fuse 4 A – 250 V
Slow Blow – 20 mm
Battery Fuse 1.6 Amp
Resettable – Electronic Fuse
Max Current Draw from
Battery (Mains Fail) 1.5 Amp Max.@ Max. Operating Temperature
Detection Circuit
Specification
Number of circuits 2,4
or 8
Max Cable resistance 40
Ù
Max Cable Capacitance
0,470 µF
Zone current quiescent
Max 5 mA
Zone current Alarm 60mA
max
End of Line Monitoring
Active EOL – CAPACITOR
BS5839 Detector removal
compliant YES provided diodes are fitted to detector base
Max. Number of Smoke/heat
detectors per zone 32 – according to EN54 pt.2
Call point resistor
value 470 to 680 Ohms
Sounder Circuit
Specification
Number of circuits 2
End of Line Resistor
value 10 K Ohms
Monitoring Open and
short circuit
Alarm Voltage 27.5 V DC
Sounder circuit Fuse
1.1 Amp resettable ( Electronic Fuse )
Max. Current available
1 Amp @ 27,5 V DC Nominal
Auxiliary Outputs
Aux power output 27.5 V
DC Nominal – Max. Current Drawn 300 mA
Fire relay Active in
Fire condition, load 30V DC/1A resistive
Fault relay Normally
closed, fail safe open on any fault, load 30V DC/1A resistive
Auxiliary Inputs
Class Change /
Evacuation Non-Latching – Voltage free contact
Remote Reset
Non-Latching – Voltage free contact
Remote Silence
Non-Latching – Voltage free contact
Dimensions
Size 278 (W) x 430 (L)
x 106 (H) mm
Weight without
batteries 1,6 Kgs
Operating Conditions
Operating Temperature 0
to +40ºC
Max Relative Humidity
85% non condensing
|